logo.gif
Fire Door Information Page

R & S Fire Doors combine the durability, security, efficiency and space saving advantages of a rolling service door with the added life and property saving benefits of automatic fire protection. Underwriters Laboratories 3-Hour/Class 'A' Label or Oversize Certificate of Compliance is furnished standard. (Refer to the Listing Summary below for conditions affecting approvals by various testing agencies. Acceptance of the listing for variations in wall construction should be verified with the building authority having jurisdiction.)

Fire Doors are designed to close automatically from a fully open position - activation of the door in the down position may cause damage. Fire Doors are not designed for use in high cycle applications - a secondary nonrated door is recommended in those situations.

fir_door.jpg

Listing Summary

Testing Agency
Underwriters Laboratories
Warnock Hersey
Factory Mutual
File Number
R-9560
R-9560
J.I. 0T0H1.AC
Hourly Rating
3 Hour
1 1/2 Hour
3 Hour
Wall Construction
Masonry
Drywall or Masonry
Masonry
Jamb Type
Concrete
Block
Brick
16 ga. (min) Steel Stud,
Steel Tube, Wood Stud, Concrete, Block, Brick
Concrete
Block
Brick
Label Size
12' Wide
12' High
120 Sq. Ft. Max.
12' Wide
12' High
120 Sq. Ft. Max.
12' Wide
12' High
120 Sq. Ft. Max.
Oversize
24' Wide
24' High
576 Sq. Ft. Max.
24' Wide
24' High
576 Sq. Ft. Max.
18' Wide
18' High
324 Sq. Ft. Max.
Jambs must be continuous members from floor to structure above. Sizes and attachment of members is to be determined to provide adequate mounting and support for the size and weight of the door.

Specifications and Options
Details
Fail Safe Release Devices
By Solid State Securities, Inc.
Distributed By R & S Manufacturing, Inc.

Standard feature on all Model SS90 release devices is an adjustable time delay of up to 30 seconds:

Model SS90-A: standard base model.
Model SS90-B: standard base model with additional relay contacts
Model SS90-B2: standard base model with additional relay contacts, and battery back-up for power lost.
Model SS09-C: standard base model with additional relay contacts, battery back-up for power lost, and additional logic board to electrically run firedoor down thru a motor operator avoiding a mechanical release.
Optional Voice Board: can be added to any model, allows a standard audio warning or an optional warning tailored to your specific needs.
Note: for additional information please consult factory.